Checking Power Elements of TXV
04 August 2015

Q: How can I determine if a TXV still has the proper charge in the power element?

A valve with a low charge (or no charge) in the power element will tend to starve the evaporator. This is because the pressure on top of the diaphragm (opening force) is reduced. To check for this, the following procedure is recommended:

1. On a valve with an external superheat adjustment, turn the adjustment nut to the full counterclockwise position. Verify that the superheat is still too high before proceeding to the next step.

2. Remove the bulb from the suction line and hold it in your hand for several minutes to warm it up. Observe the suction pressure. If the valve has charge, you should see an increase in suction pressure.

3. If no change in suction pressure occurs, it is reasonable to conclude the valve has lost its charge and must be replaced.

Note: Some valve types have removable power elements which can be replaced in lieu of replacing the entire valve. If the power element can be removed, the bulb charge can be checked by trying to depress the diaphragm with your thumb. You should NOT be able to depress this by hand. If you can, the valve has lost its charge.

Disclaimer: The information provided within this publication / eBook/ content is for general informational purposes only. While we try to keep the information up-to-date and correct, there are no representations or warranties, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the information, products, services, or related graphics contained in this publication / eBook/ content for any purpose. Any use of this information is at your own risk.